Fire Sprinklers.
HYDRANT FLOW TEST
HYDRONICS : HYDRANT FLOW TEST 5.0 FOR WINDOWS - REPORT
----------------------------------------------------------------------------
CONTRACTOR : A.B.C. FIRE PROTECTION. (510) 442-4146.
ADDRESS : 1213 Main Street, Fremont, CA. 94555.
----------------------------------------------------------------------------
File: HYDRAN14.HFT
Test Hydrant: 12 Date: 8/12/1998 Time: 14:00
Location: Pollock & Pesante
Elevation: 120 Tester: RCF
Remarks:
----------------------------------------------------------------------------
HYDRANT GAGE DIAMETER COEFF PITOT FLOW
----------------------------------------------------------------------------
1 2 2.25 in 0.88 36 Psi 797 Gpm
1 2 2.25 in 0.88 34 Psi 775 Gpm
2 3 2.5 in 0.95 30 Psi 970 Gpm
2 3 2.5 in 0.9 31 Psi 934 Gpm
3 4 1.75 in 0.97 38 Psi 546 Gpm
3 4 1.7 in 0.97 39 Psi 553 Gpm
----------------------------------------------------------------------------
Gage: 1 Static: 75 Psi Residual: 28 Psi Flow: 4575 Gpm
----------------------------------------------------------------------------
Copyright� 2008, Hydronics Engineering. (800) 845-9819.